FBM206 P0916CQ | FOXBORO Channel Isolated 8 Input
Brand/ Manufacturer:FOXBORO
Dimensions:4.5 cm x 11.5 cm x 11 cm
Weight:0.3 kg
Country Of Origin: :USA
Description:FOXBORO FBM206 P0916CQ Channel Isolated 8 Input,
Unlike the standard 200 Series FBM 206, the 1×03 frequency input module does not show a pulse count in the RAWC parameter of the AIN block, and the 1×04 pulse count module does not show a frequency reading in the PNT parameter of the AIN block. These parameters are unused and always remain at zero.For example, if point 2 for LB 1104 F is set for the counter to count down and an OPEN line fault is created for point 2, the pulse counter will reverse direction and start counting up. The opposite will occur as well; if point 2 for LB 1104 F is set for the counter to count up and an SHORT line fault is created for point 2, the pulse counter will reverse direction and start counting down.